Capteur du climat intérieur Modbus

Raumtemperatursensor mit Hygrostat
GS 30.40 mod / GS 31.40 mod

Accessories

Rückwand für Aufputz-Verkabelung 200.004

TF06 capteur de température

Overview

  • Sensors for temperature, humidity and atmospheric pressure measurement
  • Temperature sensor (Measuring range 0...+50 °C)
  • Humidity sensor (Measuring range 0...100% rel. humidity)
  • Modbus-Modes (ASCII / RTU) configurable
  • 2 Control outputs (0-10 V)
  • 2 Control outputs (FET)
  • 1 input for external temperature sensor
  • Easy installation and mounting
  • Modern and planar design [80 mm]

numéros de commande

Logo Hugo MüllerGS 30.40 mod
Raumtemperatur-
sensor mit Hygrostat
GS 30.40 mod
Raumtemperatur-
sensor mit Hygrostat
GS 31.40 mod
Raumtemperatur-
sensor mit Hygrostat mit man.
Solltemperatur-Änderung
Logo Hugo Müller
Hugo Müller GmbH & Co KG | Karlstraße 90 | D-78054 VS-Schwenningen
Tel: +49 (0) 7720 80 836 | Fax: +49 (0) 7720 80 83 88 | E-Mail: info@hugo-mueller.de | Internet: www.hugo-mueller.de
Logo Hugo Müller
Se sentir bien
page 2 / 2

Capteur du climat intérieur Modbus

Raumtemperatursensor mit Hygrostat
GS 30.40 mod / GS 31.40 mod

Order information

EANArt. No.
GS 30.40 mod
402270924658524658
GS 31.40 mod402270924659224659

Technical data

Supply voltage 20-28 V DC 50-60 Hz
Power consumption <30 mA
Bus system Modbus ASCII, Modbus RTU via RS 485
Baud rates 4800, 9600, 19200 (Default), 38400
Parity settings available None, even, odd
Sensors Temperature
relative humidity
atmospheric pressure
dew point
Outputs 2x 0-10 V max. 2mA
Outputs 2x FET Inrush current: max 1.2A
Permanent current: max. 350mA
Inputs External temperature sensor (can alternatively be used as a contact input)
Measuring range temperature 0...+50° C
Measuring range
relative humidity
0...100%
Measuring range
atmospheric pressure
300-1.100 hPa
Permitted ambient temperature 0...+50° C
Housing self-extinguishing thermoplastic
Dimensions 80,5 x 80,5 x 17 mm
Housing color studio white (similar to RAL 9016)
Specific colors on request
Mounting Wall mounting
(preferably combined with flush-mounting box)
Type of connection Screw terminals
Type of protection IP 20 (DIN EN 60529)
Class of protection III when installed according to regulations

Functions and data provided to Modbus:

Temperature Value output
Relative humidity Value output
Air pressure Value output
Dewpoint Value output
and much more...
Rights to technical amendments reserved / Technische Änderungen vorbehalten
Droits de modifications techniques réservés / Suscettibile di errori e modifiche
Logo Hugo Müller
Hugo Müller GmbH & Co KG | Karlstraße 90 | D-78054 VS-Schwenningen
Tel: +49 (0) 7720 80 836 | Fax: +49 (0) 7720 80 83 88 | E-Mail: info@hugo-mueller.de | Internet: www.hugo-mueller.de