Overview

  • Sensors for CO2, temperature, humidity and atmospheric pressure measurement
  • Detection of air quality
  • CO2-sensor (Measuring range 425...5.000 ppm air pressure compensated)
  • CO2-value is atmospheric pressure compensated
  • 2 separate temperature controls via KNX
  • Temperature control with up to 4 sensor values possible
  • Temperature sensor (Measuring range 0...50 °C)
  • Humidity sensor (Measuring range 0...100 % rel. humidity)
  • 2 VAV controls possible
  • Humidity comparator function
  • 3 analog outputs (0-10 V) and 3 binary inputs
  • 1 input for external temperature sensor
  • RGB, RGBW and Tunable White dimming function
  • KNX Secure
  • Updateable
  • Clearly structured ETS
  • Easy installation and mounting
  • Modern design for flush mounting [55 mm]
  • Fits in common switch range (55 x 55 mm)
  • GS 68.00 knx6: Setpoint temperature display optional display of further values
  • Party function
  • Frame is not included in delivery

Codice ordinativo

Logo Hugo MüllerGS 67.00 knx6
6 neutrale Tasten
GS 67.00 knx6
6 neutrale Tasten
GS 68.00 knx6
Temperaturanzeige
2 Tasten Temperatur
4 neutrale Tasten
Logo Hugo Müller
Hugo Müller GmbH & Co KG | Karlstraße 90 | D-78054 VS-Schwenningen
Tel: +49 (0) 7720 80 836 | Fax: +49 (0) 7720 80 83 88 | E-Mail: info@hugo-mueller.de | Internet: www.hugo-mueller.de
Logo Hugo Müller
Tastsensoren
Pagina 2 / 2

Pulsante 6-fold

GS 67.00 knx6 - GS 68.00 knx6

Order information

EANArt. No.
GS 67.00 knx6
402270924604224604
GS 68.00 knx6402270924608024608
GS 67.00 knx6 RAL 9005 jet black
402270924638724638
GS 68.00 knx6 RAL 9005 jet black
402270924642424642

Technical data

Supply voltage via KNX bus voltage
Bus current < 12,5 mA
Bus system KNX
Safety KNX Secure
Sensors CO2
temperature
relative humidity
atmospheric pressure
dew point
Functions Switching
blind / shutter control
dimming
scenes
values
logic function
and much more
Inputs 3 binary inputs
1 input configurable as temperature sensor input for common temperature sensors
Outputs 3 analog outputs 0-10 V
Manual operation manual adjustment of set-point temperature ±5° (increment adjustable)
Measuring range CO2-concentration 390...5.000 ppm (air pressure compensated)
Measuring range temperature 0...50 °C
Measuring range relative humidity 0...100 %
Measuring range atmospheric pressure 300...1.100 hPa
Permitted ambient temperature 0...50 °C
Housing self-extinguishing thermoplastic
Dimensions 55 x 55 mm
Housing color pure white (similar to RAL 9010) or
jet black (similar to RAL 9005)
specific colors on request
Mounting flush-mounting
Type of connection push-in connector
KNX-connector
Type of protection IP 20 (DIN EN 60529)
Class of protection III when installed according to regulations
Type of connection
analog outputs and
binary inputs
wire diameter max. 0,2-0,5 mm²
strip length 5-6 mm
Rights to technical amendments reserved / Technische Änderungen vorbehalten
Droits de modifications techniques réservés / Suscettibile di errori e modifiche
Logo Hugo Müller
Hugo Müller GmbH & Co KG | Karlstraße 90 | D-78054 VS-Schwenningen
Tel: +49 (0) 7720 80 836 | Fax: +49 (0) 7720 80 83 88 | E-Mail: info@hugo-mueller.de | Internet: www.hugo-mueller.de